KPSng(А)-FRLS cable

Fire resistant cables KPSng(А)-FRLS cable

Construction details:

KPS — fire alert system cable
ng — does not sustain combustion
(А) — construction category in terms of fire safety parameters
FR — Fire Resistant, not sustaining combustion (FE 180)
LS — Low Smoke, with low smoke and gas emission

Aapplication

In technically challenging sites, crowded sites and highly dangerous sites. Also, in other important life support systems that should maintain performance capacity during fire.

Laying and operation conditions:

  • for laying in fire protection systems (fire alert systems), alert and evacuation management systems, automated fire extinguishing systems, smoke protection systems and other systems that should sustain operation in fire).
  • for internal and external operation subject to protection from direct sunlight and fallout.
  • minimal permissible bend radius in the course of installation is 10 maximum outer diameters of the cable.
  • can be used in fire-hazardous and explosion-hazardous areas of any class.
  • shielded cables are used in buildings and structures with a high level of electromagnetic interference.
  • cables must be resistant to ambient temperatures from minus 50°C to plus 75°C and to high humidity up to 98% at temperatures up to 35°C.
  • the service life of cables in fixed installation conditions, provided that the consumer complies with the requirements for transportation, storage conditions, laying (installation) and operation, is at least 20 years.

Electric Parameters

Parameter name

Norm for the cable

with nominal conductor area, mm2

0.20

0.35

0.50

0.75

1.00

1.50

2.50

Loop resistance calculated for the length of 1 km and temperature 20°С, Ohm, not exceeding*

192.0

126.0

74.8

51.0

37.6

25.2

16.0

Conductor insulation resistance calculated for the length of 1 km and temperature 20°С, MOhm, not exceeding

100

Electrical capacity per 1 km of cable length, nF, not exceeding:








— double twisted

55.0

60

65

70

75

80

85

— twisted into a bunch

65.0

70

75

80

85

90

95

Test voltage between the conductors and between the conductors and the screen, kV:

direct/alternating current: −1min

1.4/1.0

Extinction coefficient at 1000 Hz, dB/km, not exceeding*

2.00

1.50

1.30

1.20

0.95

0.70

0.50

*Reference value

Brand

Length, m

1х2х0,2

1х2х0,35

1х2х0,5

1х2х0,75

1х2х1,0

1х2х1,5

1х2х2,5

2х2х0,2

2х2х0,35

2х2х0,5

2х2х0,75

2х2х1,0

2х2х1,5

2х2х2,5

Наш сайт использует cookies, чтобы улучшить ваш пользовательский опыт. Подробнее
Подробнее